Home > Technical Information > Hardware
|
CALL US ON
0508 966 378 |
||
| Infernoguard Approved Hardware. | |||||||||
| Mechanical Latches | |||||||||
| For fire doors to comply with AS/NZS 1905.1 or NZS 4520:2010 the following conditions apply to latches: | |||||||||
| 1) A non-self latching functions including deadlock bolts are Forbidden. | |||||||||
| 2) Material for essential latching components must have a melting point of not less than 890 degree C. | |||||||||
| Brand | Model No | Description | Note | ||||||
| Lockwood | 3570 Series including eletric | Mortise | Includes monitered Reed switch | ||||||
| Lockwood | 3570 with Smartair handles | Mortise | Intumescent Installation Required | ||||||
| Lockwood | 3P72 | Mortise | |||||||
| Legge | 990 MF Series including eletric | Mortise | |||||||
| Lockwood | KL3 & KL5 | Cylindrical | |||||||
| Schlage | A/AL series | Cylindrical | |||||||
| Legge | G2 series | Cylindrical | |||||||
| Lockwood | 530 | Tubular dead latch | |||||||
| Vingcard | Signature ANSI | Motel Lock | |||||||
| Miwa | AL5H | Motel Lock | Intumescent Installation Required | ||||||
| Cisa | Wave | Motel Lock | |||||||
| Dorma | ST9600 series | Mortise | |||||||
| Novas | 6000 series | Mortise | |||||||
| Faultless | C Series | Tubular | |||||||
| Ezyset | Commercial Lever | Tubular | Intumescent Installation Required | ||||||
| Kaba | KL 53 | Cylindrical | |||||||
| Kaba | MS2 | Mortise | |||||||
| Kaba Ilco | 790 | Motel Lock | |||||||
| Salto | Aelement - T series handles | ANSI Lock | Intumescent Installation Required | ||||||
| Head Latching Hardware | |||||||||
| Brand | Model No | Description | Note | ||||||
| Lockwood | 530 & 8530-57sc deadlatch & snib | Tubular | 1 | ||||||
| Kaba | RB 111 | Roller Catch | |||||||
| Legge | 1511 | Roller Catch | |||||||
| Samson | 515 | Roller Catch | |||||||
| Note: | |||||||||
| 1 = 70mm backset required | |||||||||
| Panic Exit Device | |||||||||
| Brand | Model No | Note | |||||||
| Dorma | PHA2000/PHB3000 | Must have DNM power bolt to head | |||||||
| Lockwood | 9000/9100 | Must have DNM power bolt to head | |||||||
| Lockwood | 9300/9400 | Must have DNM power bolt to head | |||||||
| Lockwood | 9500 | Must be through fixed and connected to a fire rated mortise | |||||||
| Briton | 379 | Must be through fixed and connected to a fire rated mortise | |||||||
| Briton | 376E/377E/378E | Must have DNM power bolt to head | |||||||
| Kaba | ED2227/ED22 | Must have DNM power bolt to head | |||||||
| Von Duprin | VD22EO-F/VD2227EO-F | Must have DNM power bolt to head | |||||||
| Von Duprin | VD99EO-F/VD9927EO-F | Must have DNM power bolt to head | |||||||
| Von Duprin | VD33A-EO/VD3327A-EO | Must have DNM power bolt to head | |||||||
| Von Duprin | VD88EO/VD8827EO | Must have DNM power bolt to head | |||||||
| Door Closers | |||||||||
| Brand | Model No | Description | Note | ||||||
| Briton | 1130 | Surface Mounted | 1 | ||||||
| Briton | 1120 | Surface Mounted | 1 | ||||||
| Briton | 200 | Surface Mounted | 1 | ||||||
| LCN | 4030 | Surface Mounted | 1 | ||||||
| LCN | 1460, 1461 | Surface Mounted | 1 | ||||||
| LCN | 1410 SE series | Surface Mounted | 4 | ||||||
| LCN | 4040 SE | Surface Mounted | 3 | ||||||
| LCN | 4031/4041 | Surface Mounted | 1 | ||||||
| Lockwood | 7726/7726 EM | Surface Mounted | 1 | ||||||
| Lockwood | 7714/7724 | Surface Mounted | 1 | ||||||
| Lockwood | 2516 | Surface Mounted | 2 | ||||||
| Dorma | TS90,91,92,93 | Surface Mounted | 2 | ||||||
| Dorma | TS93 EMF | Surface Mounted | 3 | ||||||
| Dorma | TS68,71,72,73,83 | Surface Mounted | 1 | ||||||
| Ryobi | 1550, 2550, 3550 | Surface Mounted | 1 | ||||||
| Abloy | DC250 | Surface Mounted | 2 | ||||||
| Nova | 1500 | Surface Mounted | 1 | ||||||
| Kaba | CA25 | Surface Mounted | 2 | ||||||
| Kaba | 1025 | Surface Mounted | 1 | ||||||
| Kaba | 9000 series | Surface Mounted | 1 | ||||||
| Kaba | 7000 series | Surface Mounted | 1 | ||||||
| Notes: | |||||||||
| 1 = Rack and Pinion | |||||||||
| 2 = Cam Action | |||||||||
| 3 = Electromagnetic Hold Open Cam Action | |||||||||
| 4 = Free swing connected to fire alarm | |||||||||
| Door Viewer | |||||||||
| Brand | Model No | Description | Note | ||||||
| Guardsman | G70c | ||||||||
| Schlage | DV004 | ||||||||
| Scuricraft | Brass | ||||||||
| Miscellaneous Hardware | |||||||||
| Brand | Model No | Description | Note | ||||||
| Stainless Steel | 300 high x door width | Kick Plate | (G or S) | ||||||
| LCN | SEM 7830 | Mag hold open | |||||||
| Briton | 110 DH | Mag hold open | |||||||
| Locktronic | FDH 40S | Mag hold open | |||||||
| Dorma | Matt/Mag/Maw | Mag hold open | |||||||
| Lockwood/Abloy | LC8810 | Lead cover | (DNM) | ||||||
| Locktronic | 1710 | Magnetic Lock | |||||||
| Lockwood | EM600 | Magnetic Lock | |||||||
| Schlage/Locknetics | 390+ | Magnetic Lock | |||||||
| MMcG | Grille with Steel covers | Grille 450 x 450 | (DNM) | ||||||
| Astrogrille | Grille with Steel covers | Grille 450 x 450 | (DNM) | ||||||
| Ingersoll Rand | 1195 | Pull Handles | |||||||
| Securicraft | MC10 | Hinge Bolts | |||||||
| Lockwood | Brass 100 x 100 | Power Transfer Hinge | |||||||
| DNM | Power Bolt | (DNM) | |||||||
| (DNM) = Factory fitting required | |||||||||
| (G or S) = Contact glued or screw fixed | |||||||||
| Perimeter and Door Base seals | |||||||||
| Brand | Model No | Description | Note | ||||||
| Cowdroy | CM38Si | Drop Seal | (DNM) | ||||||
| Cowdroy | CM8Si | Drop Seal | (DNM) | ||||||
| Raven | RP 35si | Drop Seal | (DNM) | ||||||
| Raven | RP 70si | Drop Seal | (DNM) | ||||||
| Raven | RP8si | Drop Seal | (DNM) | ||||||
| Raven | RP38si | Drop Seal | (DNM) | ||||||
| Raven | RP99si | Drop Seal | (DNM) | ||||||
| Raven | RP 94si | Perimeter seal | |||||||
| Raven | RP 78si | Perimeter seal | |||||||
| Raven | RP 10si | Perimeter seal | |||||||
| Raven | RP 39 | Perimeter seal | |||||||
| Raven | RP 23 | Perimeter seal | |||||||
| Raven | RP24si | Perimeter seal | |||||||